by Justin Eklund
•
26 Mar, 2021
Walk-Through Inspections Every site in Kansas MUST be completing a UST C024 to submit with their request for renewal every year. Monthly Tank Monitor Equipment Inventory Control and Reconciliation Reports Line Monitor Equipment Rectifier Spill Buckets Water Checks Overall condition of equipment Check Tank Vents Check for leaks, seeps, or damaged equipment Check hoses, nozzles, This can now be completed by a class A/B Operator Contractor for that facility. NEW Tank Testing Requirements: ALL Spill buckets MUST be tested every 3 years, unless double wall and must be monitored monthly or will be required to be tested. ALL Overfill devices MUST be tested every 3 years. All Secondary containment "sumps" MUST be tested every 3 years. Electronic Release Detection Equipment Annual testing of the automatic tank gauge - Console, Probes, & Sensors This must be completed by a Kansas Licensed Contractor and findings submitted to KDHE on an UST018. This initial test MUST also be completed by Oct. 13, 2021 and annually from that point forward.